Troubleshooting and fault elimination

8-4

UONu_^MPMQ

L

Display

Remedy

Cause

Fault

OH51

PTC monitoring (Warning)

IMotor too hot because of

excessive current or frequent

and too long acceleration

Check drive selection

IPTC not connected

Connect PTC or switch off monitoring

OV

Overvoltage

Mains voltage too high

Check voltage supply

OV

Overvoltage

Feedback operation
Braking operation

D

Increase deceleration times.

D

For operation with brake choppers:
- Check the selection and

connection of the brake resistor

- Increase the deceleration times

Earth leakage on the motor side

Check motor cable and motor for earth

fault (disconnect motor from inverter)

rSt

Faulty auto-TRIP reset

More than 8 fault messages in

10 minutes

Depends on the fault message

Pr

Faulty parameter transfer

via the operating module

PAR1 and PAR2 are defective.

It is absolutely necessary to repeat the

data transfer or load the factory setting

b f

bli

h

ll

Pr1

Faulty PAR1 transfer via

the operating module

PAR1 is defective.

data transfer or load the factory setting

before enabling the controller.

Pr2

Faulty PAR2 transfer via

the operating module

PAR2 is defective.