2 optimisation of control modes, 1 optimisation of motor-current control, Commissioning – Lenze 8210 series User Manual

Page 44

Advertising
background image

Commissioning

5-8

UONu_^MPMQ

L

5.4.2

Optimisation of control modes

5.4.2.1 Optimisation of motor-current control

Codes required

Code

Name

Possible settings

IMPORTANT

Lenze Selection

Info

C015 V/f-rated

frequency

50.0 7.5

{0.1Hz}

960.0

30.0

{0.1Hz}

960.0

(Software 2x)

(Software 1x)

C021 Slip

compensation

0

0

{1 %}

20

0

{1 %}

12

(Software 2x)

(Software 1x)

C088 Rated motor

current

*

0.0 ... 1.2 ¡ rated output current

* depends on

the unit

Input only

necessary when

motors not

C091 Motor cos

j

*

0.4

{0.1}

1.0

motors not

adapted.

Setting sequence

D

Drives with matching 4 pole standard motors 230/400 V in star connection do not

need to be adapted.After having started the drive, the controller itself detects all

further motor data.

D

The following drives can be optimized by entering the nameplate data ”rated motor

current” and ”cos

j” under C088 or C091:

- Motor one power class smaller than the motor assigned to the controller.
- Motor one or two power classes smaller than the motor assigned to the controller.
- Drives with 2, 6, 8, 10 and 12 pole standard motors.
- Drives with special motors.

D

With the slip compensation C021, you can optimize the ”sensorless speed control”

for your application.

1.If necessary, select

C014 = -4-.

(factory setting)

2.Select V/f-rated

frequency (C015).

Motor voltage

Motor

connection

C015

220/380 V

Y

52,6 Hz

230/400 V, 265/460 V, 280/480 V

Y

50 Hz

220/380 V, 230/400 V, 265/460 V, 280/480 V

D

87 Hz

380/660 V

D

52,6 Hz

400/690 V

D

50 Hz

3.If necessary, enter the

motor data of unadapted

motors (C088, C091).