2 short set-up (factory-setting), 1 switch-on sequence, Commissioning – Lenze 8210 series User Manual

Page 38: 2 short set-up (factory setting)

Advertising
background image

Commissioning

5-2

UONu_^MPMQ

L

5.2 Short set-up (Factory setting)

5.2.1

Switch-on sequence

Step
1.Switch on mains voltage

The drive controller is ready for operation after approx.

2 seconds.

2.Select the direction of rotation.

D

CW rotation:
- Apply a LOW signal to terminal E4 (0...+3V).

D

CCW rotation:
- Apply a HIGH signal to terminal E4 (+12...+30V).

3.Select the setpoint.

Apply a voltage 0...+10 V to terminal 8.

4.Enable the controller.

Apply a HIGH signal (+12...+30V) to terminal 28.

5.The drive is now operating according to factory

setting.

5.2.2

Factory setting of the most important drive
parameters

Setting

Code Factory setting

Adaption to

the

application

Operating mode

C001

-0-

Setpoint selection via terminal 8
Control via terminals
Parameter setting via 8201BB

See the Code

Table

chapter 7.2

Terminal configuration

C007

-0-

E4

E3

E2

E1

CW/CCWDC injection brake JOG1/2/3

See the Code

Table

chapter 7.2

Machine data

Chapter 5.3 ff.

Speed range

Min. field frequency

C010

0.0 Hz

Chapter 5.3.1

Speed a ge

Max. field frequency

C011 50.0 Hz

C apte 5 3

Acceleration

and

Acceleration time

C012

5.0 s

Chapter 5.3.2

and

deceleration

times

Deceleration time

C013

5.0 s

Current limit

l

Motor mode

C022 150 %

Chapter 5.3.3

Cu e t

t

values

Generator mode

C023

80 %

C apte 5 3 3

Drive performance

Chapter 5.4 ff.

Current,
torque,
power

Operating mode

C014

-4-

Motor-current control

Motor-current

control, see

chapter

5 4 2 1

power

characteristic V/f rated frequency

C015 50.0 Hz

p

5.4.2.1

V/f

characteristic

V

min

setting

C016

0 %

characteristic

control
D

with V

min

Slip compensation

C021

0 %

D

with V

min

boost, see

chapter

5.4.2.2