Configuration – Lenze 8210 series User Manual

Page 58

Advertising
background image

Configuration

7-8

UONu_^MPMQ

L

Code

IMPORTANT

Possible settings

Name

Code

IMPORTANT

Info

Selection

Lenze

Name

C125

¿*

LECOM baud rate

-0-

-0- 9600 baud
-1- 4800 baud
-2- 2400 baud
-3- 1200 baud
-4- 19200 baud

Only for LECOM

applications

C142

¿

Start condition

-1-

-0- Automatic start inhibited,

flying-restart circuit inactive

-1- Automatic start, if term. 28 HIGH,

flying-restart circuit not active

-2- Automatic start inhibited,

flying-restart circuit active

-3- Automatic start, if term. 28 HIGH,

flying-restart circuit active

C144

¿

Chopper-

frequency

reduction

821X/822X/824X

-1-

-0- No chopper-frequency reduction
-1- Automatic chopper-frequency

lowering when

J

max

- 10

°C

C161

*

Current fault

Only display

C162

*

Last fault

Only display

C163

*

Last but one fault

Only display

C164

*

Last but two fault

Only display

C170

¿

TRIP-reset

selection

-0- TRIP-reset by pressing the STP key or

LOW signal at ctrl. enable

-1- Auto-TRIP-Reset

C171 Delay for

Auto-TRIP-Reset

0

0

{1s}

60

C178

*

Operating time

Only display

C179

*

Mains switch-on

time

Only display

C377 Gain Zk-voltage

detection

822X/824X

Should only

be changed

by the Lenze

Service!

C500

*

Display factor

application datum

numerator

821X/822X/824X 2000 1

{1}

25000

C501

*

Display factor for

process variable

denominator

821X/822X/824X

10

1

{1}

25000

Show/Hide Bookmarks