Configuration – Lenze 8210 series User Manual
Page 53
![background image](/manuals/566180/53/background.png)
Configuration
UONu_^MPMQ
7-3
L
Code Name
Possible settings
IMPORTANT
Code Name
Lenze Selection
Info
IMPORTANT
C001
¿
Operating mode
-0-
-0- Setpoint selection via term. 8
Control via terminals
Parameter setting via 8201BB
-1- Setpoint selection via 8201BB or via
LECOM
Control via terminals
Parameter setting via 8201BB
-2- Setpoint selection via term. 8
Control via terminals
Parameter setting via LECOM
-3- Setpoint selection via LECOM
Control via LECOM
Parameter setting via LECOM
[C00
2]*
Parameter set
-0- Function executed
-1- Overwrite PAR1 with factory setting
-2- Overwrite PAR2 with factory setting
-3- Overwrite PAR1 and PAR2 with the
data of the operating module
-4- Overwrite PAR1 with the data of the
operating module
-5- Overwrite PAR2 with the data of the
operating module
-6- Transmit PAR1 and PAR2 to the
operating module
C004
¿
Switch-on display
-0-
-0- Field frequency f
d
-1- Controller load
-2- Motor current