Troubleshooting and fault elimination

Fault messages

8

l

103

EDBPM−H605 DE/EN/FR 7.2

8

Troubleshooting and fault elimination

8.1

Fault messages

Call up the status messages of the operating unit to display the fault message
that occurred last. (

92)

Display

Fault

Cause

Remedy

NO ERROR

No fault

PR ERROR

Faulty data
exchange

Connection between operating
unit and PC is faulty

l

Check that the connections are
firmly seated.

l

Check cable for damages

COM BROK

Communication
interrupted

Serial data cable between
operating unit and PC is
defective or not correctly
connected

l

Check Sub−D connector for correct
connection and firm seating.

l

Replace serial data cable

ASIC ko1

Communication
with system
bus (CAN)
interrupted

l

Faulty wiring (e. g. polarity)
of the system bus

l

Faulty parameterisation of
interface (baud rate,
address, identifier)

l

Check wiring of system bus (CAN)
(

^

74)

l

Check parameter setting (

^

HMI

Designer − Getting started).

ASIC ko2
ASIC ko3
ASIC ko4
RESET
SDOERR 6
SDOERR 5
SDOERR 3

8.2

Operating and display elements

)

Note!

If the lamp in the illuminated key is defective, it must be replaced by
a Lenze service technician.