Electrical installation

Wiring of system bus (CAN)

Important notes

5

l

79

EDBPM−H605 DE/EN/FR 7.2

5.4

Wiring of system bus (CAN)

5.4.1

Important notes

)

Note!

ƒ

The operating unit features an internal, hard−wired bus
terminating resistor. Therefore it has to be first or last node.

ƒ

The setting of the baud rate is described in the documentation
"HMI designer − First steps .

ƒ

Detailed information on the system bus (CAN) can be found in
the Communication Manual (CAN).

We recommend the use of CAN cables in accordance with ISO 11898−2:

CAN cable in accordance with ISO 11898−2

Cable type

Paired with shielding

Impedance

120

W (95 ... 140 W)

Cable resistance/cross−section

Cable length

£ 300 m £ 70 mW/m / 0.25 … 0.34 mm

2

(AWG22)

Cable length 301 … 1000 m

£ 40 mW/m / 0.5 mm

2

(AWG20)

Signal propagation delay

£ 5 ns/m