Appendix – Lenze EPM−H606 User Manual

Page 107

Advertising
background image

Appendix

Application example

EPM−H605 with safety PLC and EVS 93xx − ES V004 servo inverter

10

l

107

EDBPM−H605 DE/EN/FR 7.2

Terminal assignment

Terminal

Function
Lenze setting
(printed in bold)

Level / status

Technical data

X11/K32
X11/K31

Safety relay K

SR

1st disconnection
path

Pulse inhibit feedback

Open contact: Pulse
inhibit deactivated
(operation)

Closed contact: Pulse
inhibit active

X11/33

– coil of safety relay K

SR

Coil deenergised: Pulse
inhibit active

X11/34

+ coil of safety relay K

SR

Coil energised: Pulse
inhibit deactivated
(operation)

X5/28

Controller inhibit
(DCTRL−CINH)

Controller enable and controller
inhibit

LOW: Controller
inhibited
HIGH: Controller
enabled

LOW: 0 ... +3 V
HIGH: +12 ... +30 V

Input current at
+24 V:
8 mA per input

Reading and
processing of the
input signals 1/ms
(mean value)

X5/E1

Digital inputs
(freely
assignable)

CW rotation / quick stop
deactivation

HIGH

X5/E2

CCW rotation / quick stop
deactivation

HIGH

Advertising