Disconnecting from the pc, Commissioning – Lenze EPM−H606 User Manual

Page 91

Advertising
background image

Commissioning

Project transfer to the operating unit

Disconnecting from the PC

6

l

91

EDBPM−H605 DE/EN/FR 7.2

What to do

A

Switch on the PC and start the »HMI
Designer« planning tool.

B

Switch on the supply voltage for the
operating unit.

0

1

2

Port

: NET

Driver : CAN Lenze M
Ver

: 1.12

Addr

: NO ADDRESS

Error

: RESET

PROG

ESC

TRANS

PAGE

H605 TRANSFER PAGE

Main BOOT and RAM check: OK
Main FIRMWARE check

: OK

***

***

WAITING FOR DOWNLOAD FROM PC

3

The device is being initialised.

C

After initialisation, select the system
page. For this purpose, touch the display
at the corners

l

top right

0 and bottom left 1 or

l

top left

2 and bottom right 3.

The first corner to be touched must not
contain a selectable field.

The system page appears.

D

Touch the TRANS PAGE" field.

The transfer page appears.

After WAITING FOR DOWNLOAD
FROM PC is displayed, the
operating unit is ready to receive
data from the PC.

E

Transfer the desired project from the
»HMI Designer« into the operating unit.

^

HMI Designer − Getting started"

PROGRAMMING MODE" is displayed during the download.

F

After the download, the operating unit is ready for operation and can exchange data via the
system bus with the connected nodes. The project remains in memory after switching off the
supply voltage.

6.3.3

Disconnecting from the PC

1. Switch off the PC.
2. Switch off the supply voltage for the operating unit.
3. Disconnect EPZ−H110 programming adapter at the Sub−D plug and the PC.
4. Switch on the supply voltage for the operating unit.

Advertising
This manual is related to the following products: