Recorder output operation – RKI Instruments 12 VDC Beacon 200 User Manual

Page 26

Advertising
background image

22 • 12 VDC Beacon 200 Operator’s Manual

Recorder Output Operation

The output at the recorder output terminals is a 4 - 20 mA signal for each
active channel that is proportional to the detection range of the channel. A
channel that is set as CHANNEL NOT USED or CHANNEL DISABLED in
the Channel Control & Setup Program (see “Chapter 5: Channel Control
and Setup Program” on page 28) has an output of 0 mA.

There are several special circumstances where the recorder output will
behave as follows:

When a channel is in WARMUP after the 12 VDC Beacon 200 is turned
on, the recorder output will be at 4 mA.

If the 12 VDC Beacon 200 is being powered by a battery and is in low
battery alarm, the recorder output for each channel will be 0 mA.

When a channel is added or a channel type changed, the display will
indicate NEEDS CALIBRATION for that channel when the 12 VDC
Beacon 200 is first turned on and will continue to indicate this until the
channel is calibrated. In this situation, the recorder output will be at 3.2
mA until the channel is calibrated.

If a channel goes into a fail condition, the recorder output will be 0 mA.

If you enter any of the instrument programs, such as the Calibration
Program, the recorder output will hold at the value it was at when you
entered the program was entered until you return to normal operation.

Advertising