RKI Instruments 12 VDC Beacon 200 User Manual

Page 28

Advertising
background image

24 • 12 VDC Beacon 200 Operator’s Manual

NOTE: You can select normally energized (NE) or normally de-energized

(NDE) channel relay settings in the Channel Control & Setup
menu. The following sections describe the default setting for the
channel relays which is NDE.

Common alarm 1 and alarm 2 relays are factory-set as NDE, and
the common fail relay is factory set as NE. The common relays’
NE/NDE settings are not user-adjustable.

Alarm 1 Condition

This section describes the audible and visual indications for an alarm 1
condition and suggests response to an alarm 1 condition.

Alarm 1 Condition Indications

When the gas reading of an active channel reaches the alarm 1 setpoint,
the 12 VDC Beacon 200 senses an alarm 1 condition. The 12 VDC Beacon
200 alerts you to an alarm 1 condition as follows:

The ALARM 1 light turns on.

The gas reading in alarm 1 condition flashes and alternates with the
ALARM-1 message.

The buzzer sounds a Pulsing tone.

The common alarm 1 relay energizes.

The applicable alarm 1 channel relay energizes.

Responding to an Alarm 1 Condition

This section suggests response to an alarm 1 condition.

1. Follow your established procedure for a low level combustible or toxic

gas condition or a decreasing oxygen content condition.

2. Oxygen alarms are self-resetting and will automatically clear when the

oxygen rises above the alarm 1 setpoint.

3. Alarms for all other gas types are latching. After the gas reading falls

below the alarm 1 setpoint, press the reset switch to reset the alarm 1
circuit. Resetting the alarm 1 circuit silences the buzzer, turns off the
ALARM 1 light, resets the channel display, and de-energizes the
common and channel alarm 1 relays.