RKI Instruments 12 VDC Beacon 200 User Manual

Page 29

Advertising
background image

12 VDC Beacon 200 Operator’s Manual • 25

NOTE: To silence the buzzer while in an alarm 1 condition, press the

reset switch.

You cannot de-energize the alarm 1 relays and consequently the
strobe/horn until the gas reading falls below the alarm 1 setpoint.

Alarm 2 Condition

This section describes the audible and visual indications for an alarm 2
condition and suggests response to an alarm 2 condition.

Alarm 2 Condition Indications

When the gas reading of an active channel reaches the alarm 2 setpoint,
the 12 VDC Beacon 200 senses an alarm 2 condition. The 12 VDC Beacon
200 alerts you to an alarm 2 condition as follows:

The ALARM 2 light turns on.

The gas reading in alarm 2 condition continues to flash and alternates
with the ALARM-2 messages.

The buzzer sounds a Pulsing tone.

The common alarm 2 relay energizes.

The applicable alarm 2 channel relay energizes.

Responding to an Alarm 2 Condition

This section suggests response to an alarm 2 condition.

1. Follow your established procedure for a high level combustible or toxic

gas condition or an increasing oxygen content condition.

2. Oxygen alarms are self-resetting and will automatically clear when the

oxygen rises above the alarm 2 setpoint.

3. Alarms for all other gas types are latching. After the gas reading falls

below the alarm 2 setpoint, press the reset switch to reset the alarm
circuit. Resetting the alarm circuit turns off the ALARM 2 light, and de-
energizes the common and channel alarm 2 relays.

NOTE: To silence the buzzer while in an alarm 2 condition, press the

reset switch.

You cannot de-energize the alarm 2 relays until the gas reading
falls below the alarm 2 setpoint.

Advertising