Alarm indications – RKI Instruments 12 VDC Beacon 200 User Manual

Page 27

Advertising
background image

12 VDC Beacon 200 Operator’s Manual • 23

Alarm Indications

This section describes the 12 VDC Beacon 200 in alarm 1, alarm 2, and fail
conditions and suggests response to these conditions. Table 6 below lists
the alarm indications for each condition.

NOTE: The 12 VDC Beacon 200 includes alarm on and alarm off delay

settings for each channel and level of gas alarm. The alarm
indications described in this section operate according to the
factory set delay settings. See “Configure Channel Settings Menu”
on page 30 for all the factory settings.

Table 6: Visual and Audible Alarm Indications

Condition

Cause

Visual Indication(s)

Audible

Indication

Alarm 1

1

Increasing (decreasing for O

2

) gas

reading at or above (below for O

2

) the

alarm 1 setpoint

ALARM 1 light is on

Gas reading flashes and
alternates with ALARM-1
message

Strobe/horn turns on

Pulsing tone

Alarm 2

1

Increasing gas reading at or above the
alarm 2 setpoint

ALARM 2 light is on

Gas reading flashes and
alternates with ALARM-2
message

Pulsing tone

Fail

Disconnected or misconnected
detector wiring

Display reading below -10% of full
scale or lower

Defective components

FAIL light is on

FAIL

message flashes in

place of gas reading

Steady tone

Low Battery

Dead 12 VDC battery.

FAIL light is on

SUPPLY VOLTAGE IS TOO
LOW

LOW POWER

STANDBY

message and

actual voltage of incoming
DC power

None

NOTE: Under typical operating conditions, there will be no low power alarm. Most 12 VDC power sources’ output voltage
will decrease too quickly in a low power condition for the 12 VDC Beacon 200 to recognize a low power condition before it
shuts down.

*

1

If the 12 VDC Beacon 200 is in both an alarm 1 and an alarm 2 condition, both alarm lights are on and the

display alternates between the gas reading and the ALARM-1 ALARM-2 message.

Advertising