RKI Instruments Beacon 200 RIg Monitor, H2S/H2S User Manual

Page 16

Advertising
background image

11 • Beacon 200 Rig Monitor Operator’s Manual

DC In Terminal Strip. The DC in terminal strip is a 3-point terminal strip
located above the controller terminal strip (see Figure 1). It facilitates
wiring from the 12 VDC battery. The 50 foot battery cable is factory
wired to this terminal strip. Table 4 lists the function of each terminal.

Relays

The Rig Monitor includes four channel relays (two per channel) and three
common relays. Both sets of relays are single-pole, double-throw (SPDT)
and are rated for 10 amps at 250 VAC (resistive).

NOTE: You can select normally energized (NE) or normally de-energized

(NDE) settings for each channel in the Channel Control and Setup
program. This section describes the default setting: normally de-
energized.

The alarm 1 and alarm 2 common relays are factory-set as NDE
and the fail common relay is factory-set as NE. The alarm 1, alarm
2, and fail common relays’ NE/NDE settings are not user-
adjustable.

Channel relays. The four channel relays are above the alarm terminal
strip (see Figure 1). These relays are dedicated to specific channels
and alarm levels.

For example, the channel 1, alarm 1 relay energizes if channel 1
recognizes an alarm 1 condition. Figure 4 below illustrates the
allocation of the channel relays.

Table 4: Terminal Assignments for the AC In Terminal Strip

Terminal

Connects to:

+

White wire from battery cable

-

Black wire from battery cable

Earth ground, factory wired

K5

K6

K7

Channel 2, Alarm 1

Channel 1, Alarm 2

Channel 1, Alarm 1

K1

K2

K3

Common Alarm 1

Common Alarm 2

Common Fail

K4

Channel 2, Alarm 2

Figure 5. Beacon 200 Rig Monitor Channel Relay Allocation