RKI Instruments Beacon 200 RIg Monitor, H2S/H2S User Manual

Page 28

Advertising
background image

23 • Beacon 200 Rig Monitor Operator’s Manual

NOTE: You can select normally energized (NE) or normally de-energized

(NDE) channel relay settings in the Channel Control & Setup
menu. The following sections describe the default setting for the
channel relays which is NDE.

Common alarm 1 and alarm 2 relays are factory-set as NDE, and
the common fail relay is factory set as NE. The common relays’
NE/NDE settings are not user-adjustable.

Alarm 1 Condition

This section describes the audible and visual indications for an alarm 1
condition and suggests response to an alarm 1 condition.

Alarm 1 Condition Indications

When the gas reading of an active channel reaches the alarm 1 setpoint,
the Rig Monitor senses an alarm 1 condition. The Rig Monitor alerts you to
an alarm 1 condition as follows:

The ALARM 1 light turns on.

The gas reading in alarm 1 condition flashes and alternates with the
ALARM-1 message.

The buzzer sounds a Pulsing tone.

The common alarm 1 relay energizes and the strobe/horn activates.

The applicable alarm 1 channel relay energizes.

Responding to an Alarm 1 Condition

This section suggests response to an alarm 1 condition.

1. Follow your established procedure for a low level H

2

S condition.

2. Alarms are latching. After the gas reading falls below the alarm 1

setpoint, press the reset switch to reset the alarm 1 circuit. Resetting
the alarm 1 circuit silences the buzzer, turns off the ALARM 1 light,
resets the channel display, de-energizes the common and channel
alarm 1 relays, and turns off the strobe/horn.

NOTE: To silence the buzzer while in an alarm 1 condition, press the

reset switch.

You cannot de-energize the alarm 1 relays and consequently the
strobe/horn until the gas reading falls below the alarm 1 setpoint.

Advertising