connector at the bottom of the terminal PCB is used to connect the terminal PCB to the
control PCB with a ribbon cable. A 5 position connector on the left side of the terminal
PCB is used by factory or field service personnel to program the M2. On the combustible
and CO

2

versions of the M2, a factory adjust pot just above the programming connector is

used to set the detector current.

Power/Signal Terminal Strip

The power/signal terminal strip is a three position plug-in style terminal strip located at
the top of the left terminal column. It is used to connect 24 VDC power to the M2 and to
connect the 4 - 20 mA output signal to a device.

The signal output, the S terminal, does not have to be connected for the M2 to function.
The S terminal is used if you want to connect the 4 - 20 mA output signal to another device
such as a gas monitoring controller, chart recorder, or programmable controller (PLC).

Detector Terminal Strip

The detector terminal strip is a four position plug-in style terminal strip and is the middle
terminal strip in the left terminal column. For a combustible or CO

2

M2, all four terminals

are used to connect the detector to the M2. For a toxic or oxygen M2, only two of the
terminals are used for connecting a detector: two terminals are dedicated for connecting a
toxic detector and two are dedicated for connecting an oxygen detector (only one detector
can be installed).

Figure 10: Detector Terminal Strip

NOTE:

The detector is factory-wired to the M2. See “Wiring the M2 Transmitter” on
page 18 for all wiring procedures related to M2.

Modbus Terminal Strip

The Modbus terminal strip is a three position plug-in style terminal strip and is the
bottom terminal strip in the left terminal column. It allows connection of the M2 into a
Modbus network.

C NC NO

C NC NO

C NC NO

ALARM 2

ALARM 1

F

AIL

A B C

RS 485

PWR/SIG

LEL

S

R

W G B

C NC NO

C NC NO

C NC NO

ALARM 2

ALARM 1

F

AIL

A B C

A B C

RS 485

RS 485

PWR/SIG

PWR/SIG

T

O

XIC O

X

Y

T

O

XIC O

X

Y

S

S

Comb/CO

2

Detector

Terminal Strip

Oxy/Toxic Detector

Terminal Strip

A B C

RS 485

PWR/SIG

LEL

S

R

W G B

Advertising