M2 Transmitter Operator’s Manual

Register 19

Register 19 is for clearing change flags. When parameters are changed at the M2, a flag is
raised at the controller. This register can be used to clear those flags.

Table 18:

Register 19, Clear Change Flags

Register 20

Register 20 is the AutoZero Disable.
0=AutoZero Enabled
1=AutoZero Disabled

Register 21

Register 21 is the Remote Configuration Register.
0=No Remote Configuration
1=Reset Alarm

Bit(s)

Value & Field

[15:2]

Unused

[1]

Write “1” to this bit to clear “Gas Type Changed” flag

[0]

Write “1” to this bit to clear “Configuration Changed” flag