M2 Transmitter Operator’s Manual

12

Relay Terminal Strips

The right column of terminal strips consists of, from top to bottom, the fail, alarm 1, and
alarm 2 relay terminal strips. They are three-position plug-in style terminal strips. The
relay terminal strips are used to connect devices such as lights and horns that are
controlled by the relay contacts. The relay contacts are rated at 115 VAC, 5 amps. The relay
contacts may also be used to control higher rated relays.

Termination Jumper

A two pin header with a termination jumper installed is located below the Modbus
terminal strip. The jumper has no function unless the M2 is wired into a Modbus
installation. See “Chapter 8: RS-485 Modbus Output” on page 50 for a description of using
the M2 in a Modbus system.

Control PCB

The LCD display and control switches are located on the control PCB. It is installed on top
of the terminal PCB by lining up its three spacing standoffs with the banana jacks in the
terminal PCB mounting standoffs and pushing it onto the banana jacks. The jacks retain
the control PCB.

LCD Display

The LCD display is located at the top of the control PCB. It indicates the current gas
reading and displays messages and parameters in the M2’s programs.

Control Buttons

The M2 includes three push button switches that allow you to enter the M2’s operating
modes, navigate through the modes, update settings, and save changes to the settings.
The push button switches are located along the bottom edge of the control PCB (see
Figure 9). The UP/YES button is on the left, the DOWN/NO button is in the middle, and
the ENTER button is on the right.

Just above each push button switch is a magnetic switch with the same function as the
push button switch below it. The magnetic switches are for use in non-intrusive
calibration. They are actuated by bringing the magnetic wand close enough to them to

Table 3: M2 Control Button Functions

Switch

Function

UP (YES)

Saves settings

Changes the displayed setting

Enters the Calibration Program

Enters Gas Type Mode (press with DOWN/NO button)

Enters Configuration Mode (press with ENTER button)

DOWN (NO)

Cancels setting changes

Changes the displayed setting

Enters Gas Type Mode (press with UP/YES button)

Enters Modbus Mode (press with ENTER button)

Displays the Information Screen

ENTER

Initiates operations

Enters Configuration Mode (press with UP/YES button)

Enters Modbus Mode (press with DOWN/NO button)

Functions as an alarm reset switch