M2 Transmitter Operator’s Manual

Fail
Condition

• M2 indicates a fail

condition.

• Controller

indicates a fail

condition

• The detector wiring

to the terminal PCB

is disconnected or

misconnected.

• The wiring from the

M2 to the controller

is disconnected or

misconnected.

• The detector fresh

air signal is low

enough to cause a

fail condition.

• The detector is

malfunctioning.

• The terminal or

display PCB is

malfunctioning.

1. Verify that the detector wiring is

correct and secure.

2. Verify that the wiring between the

M2 and the controller is correct

and secure.

3. Calibrate the M2.
4. If the fail condition continues,

replace the detector.

5. If the fail condition continues,

contact RKI for further

instruction.

Slow or No
Response/
Difficult or
Unable to
Calibrate

• M2 responds

slowly or does not

respond to

response test.

• Unable to

successfully set

the fresh air or

span (zero for

oxygen) reading

during

calibration.

• M2 requires

frequent

calibration.

Note:

See “Calibration

Frequency” on page 40 for
calibration frequency
guidelines.

• The calibration

cylinder is low, out-

dated, or defective.

• The detector is

malfunctioning.

• The terminal PCB is

malfunctioning.

1. Verify that the calibration cylinder

contains an adequate supply of a

fresh test sample.

2. If the calibration/response

difficulties continue, replace the

detector.

3. If the calibration/response

difficulties continue, contact RKI

for further instruction.

Table 9:Troubleshooting the Combustible Gas Detector (Continued)

Condition

Symptom(s)

Probable Causes

Recommended Action