Troubleshooting – RKI Instruments M2 Series User Manual

Page 43

Advertising
background image

M2 Transmitter Operator’s Manual

38

Troubleshooting

The troubleshooting guide describes symptoms, probable causes, and recommended
action for problems you may encounter with the M2.

NOTE:

This troubleshooting guide describes M2 problems only. If the M2 is connected to
a controller, see the controller operator’s manual for problems you may
encounter with the controller.

Table 9:Troubleshooting the Combustible Gas Detector

Condition

Symptom(s)

Probable Causes

Recommended Action

No Power

The display backlight
is off and the display
screen is blank.

• The power wiring is

disconnected or

misconnected.

• The display cable is

disconnected or

misconnected.

1. Verify that the wiring to the

power source or controller is

correct and secure.

2. Verify that the ribbon cable

connecting the terminal PCB to

the control PCB is securely

installed. This ribbon cable plugs

into a connector on the top edge

of the control PCB and on the

bottom of the terminal PCB.

3. If the power difficulties continue,

contact RKI for further

instruction.

Frequent or
Suspect
Alarms

The M2 alerts you to
frequent or suspect
alarms while the
fresh air readings
remain on zero (20.9
for oxygen).

• The M2 is

experiencing false

readings due to RFI

or EMI.

• The detector wiring

is disconnected,

misconnected, or

intermittent.

1. Verify that the M2 wiring is

properly shielded. See “Wiring

the M2 Transmitter” on page 18.

2. Verify that the detector wiring is

correct and secure.

3. Increase the alarm on delay

setting in Configuration Mode.

4. If the frequent or suspect alarm

difficulties continue, contact RKI

for further instruction.

Flickering
Display

The display reading
flickers often.

• The M2 is

experiencing false

readings due to RFI

or EMI.

• The noise filter

setting is too low.

• The zero

suppression setting

is too low.

• The display screen

is malfunctioning.

1. Verify that the M2 wiring is

properly shielded. See “Wiring

the M2 Transmitter” on page 18.

2. Verify that the detector wiring is

correct and secure.

3. Increase the filter setting in

Configuration Mode.

4. Increase the zero suppression

setting in Configuration Mode.

5. If the display difficulties continue,

contact RKI for further

instruction.