M2 Transmitter Operator’s Manual

Register 12

Register 12 is the range (full scale readout).

Register 13

Register 13 is the alarm 1 set point.
The decimal point location is the same as specified in Register 1.

Register 14

Register 14 is the alarm 2 set point.
The decimal point location is the same as specified in Register 1.

Registers 15 - 19

Registers 15 - 19 are the Gas Name ASCII String (NULL Terminated).

Registers 20 - 22

Registers 20 - 22 are the Gas Units String (NULL Terminated).

Register 23

Register 23 is the alarm 1 trigger.
0=Decreasing
1=Increasing

Register 24

Register 24 is the alarm 1 normal relay state.
0=Normally De-Energized
1=Normally Energized

Register 25

Register 25 is the alarm 1 relay reset.
0=Latching
1=Self-Resetting

Register 26

Register 26 is the alarm 1 ON delay.
Integer values are in seconds.

Register 27

Register 27 is the alarm 1 OFF delay.
Integer values are in seconds.

Register 28

Register 28 is the alarm 2 trigger.
0=Decreasing
1=Increasing

Register 29

Register 29 is the alarm 2 normal relay state.
0=Normally De-Energized
1=Normally Energized