M2 Rig Monitor Operator’s Manual

20

Alarm 2 Condition

Alarm 2 Condition Indications

When the gas reading reaches the alarm 2 setpoint, the Rig Monitor senses an alarm 2
condition. The Rig Monitor alerts you to an alarm 2 condition as follows:

The A2 LED turns on.

The gas reading alternates with the ALARM-2 message.

The alarm 2 relay energizes.

NOTE:

If the M2 Rig Monitor is in both an alarm 1 and alarm 2 condition, both the A1
and A2 LEDs will be on, the gas reading will alternate with the ALMS 1&2
message, and both alarm relays will energize.

Responding to an Alarm 2 Condition

1.

Follow your established procedure for a high level H

2

S condition.

2.

After the gas reading falls below the alarm 2 setpoint, press the ENTER button to reset
the alarm circuit. Resetting the alarm circuit turns off the A2 light, resets the LCD, and
de-energizes the alarm 2 relay.

NOTE:

If the ENTER button is pressed while the M2 Rig Monitor is in an alarm 2
condition, the A2 LED will flash but all other indications will remain
unchanged.

You cannot de-energize the alarm 2 relay until the gas reading falls below the
alarm 2 setpoint.

Fail Condition

Fail Condition Indications

The Rig Monitor indicates a fail condition for any of the following:

The detector wiring is disconnected or incorrectly connected.

The display reading is -10% of full scale or lower.

When the Rig Monitor senses a fail condition, it alerts you as follows:

The F LED turns on.

The gas reading is replaced by the FAIL message.

The fail relay de-energizes.

NOTE:

The fail alarm has a 30 second delay.

Responding to a Fail Condition

1.

Verify that the detector wiring is correctly and securely connected.

2.

Verify that the replaceable plug-in sensor in the detector housing is properly installed.