M2 Rig Monitor Operator’s Manual

Function Code 16: Write Registers

There are 21 registers in Function Code 16 that can be used to write to the Rig Monitor.
This manual only describes Register 16 because it can be used to reset an alarm condition.
For a complete description of Function Code 16, request Appendix B from RKI
Instruments, Inc.

Register 16

Register 16 performs the same functions as the buttons on the Rig Monitor. Among other
things, it is useful for remotely silencing alarms. With the Rig Monitor in an alarm
condition, bit [0] can be used to silence it.

Table 10: Register 16, Button Function

NOTE:

Register 40, the remote configuration register, must be set to 1 or 2 in order for
Register 16 to work.

Bit

Value & Field

[0]

ENTER (also used for “Alarm Reset”)
0=Not Pressed
1=Pressed

[1]

DOWN/NO
0=Not Pressed
1=Pressed

[2]

UP/YES
0=Not Pressed
1=Pressed

[3]

HOLD Status
0=Button(s) Pressed and Released
1=Button(s) Pressed and Held