M2 Rig Monitor Operator’s Manual

26

sample tubing from the calibration cup/splash guard hose barb.

10. When the Rig Monitor display reading falls below the alarm setpoints, return it to

normal operation.

11. Store the components of the calibration kit in a safe place.

Quarterly

Calibrate the Rig Monitor as described in “Calibration” on page 28.

Troubleshooting

The troubleshooting guide describes symptoms, probable causes, and recommended
action for problems you may encounter with the M2 Rig Monitor.

Table 5:Troubleshooting the M2 Rig Monitor

Condition

Symptom(s)

Probable Causes

Recommended Action

No Power

The display backlight
is off and the display
screen is blank.

• The power wiring

at the Rig Monitor

is disconnected or

misconnected.

• The display cable is

disconnected or

misconnected.

• The battery is dead

or at a very low

voltage.

1. Verify that the wiring to the

power source is correct and

secure.

2. Verify that the ribbon cable

connecting the terminal PCB to

the control PCB is securely

installed. This ribbon cable plugs

into a connector on the top edge

of the control PCB and on the

bottom of the terminal PCB.

3. If the power difficulties continue,

contact RKI for further

instruction.

Frequent or
Suspect
Alarms

The Rig Monitor
alerts you to frequent
or suspect alarms
while the fresh air
readings remain on
zero.

• The Rig Monitor is

experiencing false

readings due to RFI

or EMI.

• The detector wiring

is disconnected,

misconnected, or

intermittent.

1. Verify that the Rig Monitor wiring

is properly shielded. See “Wiring

the M2 Rig Monitor” on page 12.

2. Verify that the detector wiring is

correct and secure.

3. Increase the alarm on delay

setting in Configuration Mode.

4. If the frequent or suspect alarm

difficulties continue, contact RKI

for further instruction.

Flickering
Display

The display reading
flickers often.

• The Rig Monitor is

experiencing false

readings due to RFI

or EMI.

• The noise filter

setting is too low.

• The zero

suppression setting

is too low.

• The display screen

is malfunctioning.

1. Verify that the Rig Monitor wiring

is properly shielded. See “Wiring

the M2 Rig Monitor” on page 12.

2. Verify that the detector wiring is

correct and secure.

3. Increase the filter setting in

Configuration Mode.

4. Increase the zero suppression

setting in Configuration Mode.

5. If the display difficulties continue,

contact RKI for further

instruction.