RKI Instruments GD-K71D User Manual
Page 29

PT2E-1052
28
5−5−3.Confirmation of alarm level
This is used to check alarm levels.
①Press MODE switch for above 3 seconds,
and maintenance mode starts.
②Select 「1-2」 with FLOW ADJ./▲▼
switch.
③Press TEST/SET switch to check
the 1st alarm level (ALM 1).
Press TEST/SET switch again to
check the 2nd alarm level (ALM 2).
④To return detection mode, press
MODE switch for above 3 seconds.
SKIP light turns OFF which
shows detection mode.
● ○ ○ ◎
PW/TR ALM1 ALM2 SKIP
● ○ ◎ ◎
PW/TR ALM1 ALM2 SKIP
After completion of this operation, be sure to return detection mode(Only PW/TR light turns
ON) by pressing MODE switch.
When leave it alone on maintenance mode, this returns detection mode automatically after
10 hours.
● ○ ○ ○
PW/TR ALM1 ALM2 SKIP
WARNING
CAUTION
To change alarm levels, please contact with our nearest agent or RIKEN KEIKI.
* Note
● ◎ ○ ◎
PW/TR ALM1 ALM2 SKIP
● ○ ○ ◎
PW/TR ALM1 ALM2 SKIP