Setting a subnet mask using parameters – Rockwell Automation 20-COMM-M Modbus/TCP Adapter User Manual

Page 29

Advertising
background image

Configuring the Adapter

3-7

20-COMM-M Modbus/TCP Adapter User Manual

Publication 20COMM-UM014C-EN-P

Setting a Subnet Mask Using Parameters

1. Verify that Parameter 03 - [BOOTP] is set to “0” (Disabled). This

parameter must be set to Disabled to configure the subnet mask using
the adapter parameters.

2. Set the value of Parameters 08 - [Subnet Cfg 1] through 11 - [Subnet

Cfg 4] to the desired value for the subnet mask.

Figure 3.7

Example Subnet Cfg 1 LCD HIM Screen

3. Reset the adapter (see

Resetting the Adapter on page 3-12

).

Setting a Gateway Address for the Adapter Using Parameters

1. Verify that Parameter 03 - [BOOTP] is set to “0” (Disabled). This

parameter must be set to Disabled to configure the gateway address
using the adapter parameters.

2. Set the value of Parameters 12 - [Gateway Cfg 1] through 15 -

[Gateway Cfg 4] to the IP address of the gateway device.

Figure 3.8

Example Gateway Cfg 1 LCD HIM Screen

3. Reset the adapter (see

Resetting the Adapter on page 3-12

).

Port 5 Device

20-COMM-M

Parameter #: 08
Subnet Cfg 1

0

0 <> 255

Default = 0.0.0.0

255 . 255 . 255 . 255

[Subnet Cfg 1]

[Subnet Cfg 2]

[Subnet Cfg 3]

[Subnet Cfg 4]

Port 5 Device

20-COMM-M

Parameter #: 12
Gateway Cfg 1

0

0 <> 255

Default = 0.0.0.0

255 . 255 . 255 . 255

[Gateway Cfg 1]

[Gateway Cfg 2]

[Gateway Cfg 3]

[Gateway Cfg 4]