B-4

Adapter Parameters

20-COMM-M Modbus/TCP Adapter User Manual
Publication 20COMM-UM014C-EN-P

24 [DPI I/O Cfg]

Sets the I/O that is transferred through the adapter.

Default:

xxx0 0001

Bit Values:

0 = I/O disabled
1 = I/O enabled

Type:

Read/Write

Reset Required: Yes

25 [DPI I/O Act]

Displays the I/O that the adapter is actively
transmitting. The value of this parameter will usually be
equal to the value of Parameter 24 - [DPI I/O Cfg].

Default:

xxx0 0001

Bit Values:

0 = I/O disabled
1 = I/O enabled

Type:

Read Only

26 [Flt Cfg Logic]

Sets the Logic Command data that is sent to the drive
if Parameter 23 - [Comm Flt Action] is set to “4”
(Send Flt Cfg) and communications are disrupted.

The bit definitions will depend on the product to which
the adapter is connected. See

Appendix C

or the

documentation for the drive being used.

Default:

0000 0000 0000 0000

Minimum:

0000 0000 0000 0000

Maximum:

1111 1111 1111 1111

Type:

Read/Write

Reset Required: No

27 [Flt Cfg Ref]

Sets the Reference data that is sent to the drive if
Parameter 23 - [Comm Flt Action] is set to “4” (Send
Flt Cfg) and communications are disrupted.

Default:

0

Minimum:

0

Maximum:

4294967295

Type:

Read/Write

Reset Required: No

Important: If the drive uses a 16-bit
Reference, the most significant word of
this value must be set to zero (0) or a
fault will occur.

28
29
30
31
32
33
34
35

[Flt Cfg A1 In]
[Flt Cfg A2 In]
[Flt Cfg B1 In]
[Flt Cfg B2 In]
[Flt Cfg C1 In]
[Flt Cfg C2 In]
[Flt Cfg D1 In]
[Flt Cfg D2 In]

Sets the data that is sent to the Datalink in the drive if
Parameter 23 - [Comm Flt Action] is set to “4” (Send
Flt Cfg) and communications are disrupted.

Default:

0

Default:

0

Default:

0

Default:

0

Default:

0

Default:

0

Default:

0

Default:

0

Minimum:

0

Maximum:

4294967295

Type:

Read/Write

Reset Required: No

Important: If the drive uses 16-bit
Datalinks, the most significant word of
this value must be set to zero (0) or a
fault will occur.

36 [Web Enable]

Displays the setting of the adapter Web Pages Switch
(SW2 in

Figure 2.1

) when the adapter was last reset.

Default:

0 = Disabled

Values:

0 = Disabled
1 = Enabled

Type:

Read Only

Parameter
No. Name and Description

Details

Bit
Definition

No

t Us

ed

No

t Us

ed

No

t Us

ed

Da

ta

link

D

Da

ta

link

C

Da

ta

link

B

Da

ta

link

A

Cmd/Ref

Default

x

x

x

0

0

0

0

1

Bit

7

6

5

4

3

2

1

0

Bit
Definition

Not Used

Not Used

Not Used

Dat

alink D

Dat

alink C

Dat

alink B

Dat

alink A

Cmd/

Ref

Default

x

x

x

0

0

0

0

1

Bit

7

6

5

4

3

2

1

0