Rockwell Automation 20-COMM-M Modbus/TCP Adapter User Manual

Page 44

Advertising
background image

4-8

Using Modbus/TCP Function Codes

20-COMM-M Modbus/TCP Adapter User Manual
Publication 20COMM-UM014C-EN-P

Table 4.H

shows the Logic Status register used for reading 16-bit status

fields or multiple decimal values.

Table 4.H Logic Status Register

To view the Feedback, you must read the decimal values of register
addresses 10023 and 10024 (

Table 4.I

) using Function Code 03 or 23. For

details about how the Feedback is scaled, refer to

page 4-6

.

Table 4.I

Feedback Registers

10

9

Local Control

Register Address

11

10

12

11

10

12

11

0

0

0

= Port 0 (TB)

0

0

1

= Port 1

0

1

0

= Port 2

0

1

1

= Port 3

1

0

0

= Port 4

1

0

1

= Port 5

1

1

0

= Port 6

1

1

1

= No Local

13

12

Reference

Register Address

14

13

16

15

14

13

15

14

0

0

0

0

= Ref A Auto (Par. 90)

16

15

0

0

0

1

= Ref B Auto (Par. 93)

0

0

1

0

= Preset 2 Auto

0

0

1

1

= Preset 3 Auto

0

1

0

0

= Preset 4 Auto

0

1

0

1

= Preset 5 Auto

0

1

1

0

= Preset 6 Auto

0

1

1

1

= Preset 7 Auto

1

0

0

0

= Term Blk Manual

1

0

0

1

= DPI 1 Manual

1

0

1

0

= DPI 2 Manual

1

0

1

1

= DPI 3 Manual

1

1

0

0

= DPI 4 Manual

1

1

0

1

= DPI 5 Manual

1

1

1

0

= DPI 6 manual

1

1

1

1

= Jog Ref

Register
Address

Description

Values

10021

Logic Status Word

16-bit word. Bit definitions for PowerFlex 70/700 drives are in

Table 4.G

. For other products, refer to their documentation.

Register
Address

Description

Values

10023

(1)

(1)

For a 16-bit Feedback, you must read the complete 32-bit value.

Feedback Lo

Bit 0…15 of 32-bit Feedback or the whole 16-bit Feedback

10024

Feedback Hi

Bit 16…31 of 32-bit Feedback

Table 4.G Logic Status Registers (to Controller from Drive) (Continued)

Register
Address

Logic Status Bit PowerFlex 70/700 Example

Description

Values