Setting the Fault Configuration Parameters

If you set Parameter 23 - [Comm Flt Action] to “Send Flt Cfg,” the values
in the following parameters are sent to the drive after an I/O
communications fault and/or idle fault occurs. You must set these
parameters to values required by your application.

Changes to these parameters take effect immediately. A reset is not required.

Setting the Message I/O
Timer

Set Parameter 19 - [Msg I/O Timer] to a communication loss timeout
period suitable for your application. By default, the timeout is set to five (5)
seconds. You can increase or decrease this value. Alternatively, you can set
the value to zero (0) to disable this timeout feature so that the adapter does
not detect communication losses.

Figure 3.12 Example Ref Adjust LCD HIM Screen

Changes to this parameter takes effect immediately. A reset is not required.

Parameter

Description

26 - [Flt Cfg Logic] A 16-bit value sent to the drive for Logic Command.
27 - [Flt Cfg Ref]

A 32-bit value (0…4294967295) sent to the drive as a Reference or Datalink.

Important: If the drive uses a 16-bit Reference or 16-bit Datalinks, the most
significant word of the value must be set to zero (0) or a fault will occur.

28 - [Flt Cfg x1 In]

through

35 - [Flt Cfg x2 In]

!

ATTENTION: Risk of injury or equipment damage exists.
Parameter 19 - [Msg I/O Timer] lets you determine how long it
will take the adapter to detect network communication losses. By
default, this parameter sets the timeout to five (5) seconds. You
can set it so that the duration is shorter, longer, or disabled. When
set to disabled, this also disables adapter Parameter 23 - [Comm
Flt Action]
. Therefore, a communications fault action will be
ignored. Take precautions to ensure that the setting does not
create a risk of injury or equipment damage. When
commissioning the drive, verify that your system responds
correctly to various situations (for example, a disconnected
cable).

Port 5 Device

20-COMM-M

Parameter #: 19
Msg I/O Timer

5

sec

0 <> 180

Default = 5 sec