Install Components
1. Install the new T-Comm board.
2. Verify the board is locked into all seven locking tabs.
3. Carefully bend the T-Comm grounding tab until it is flush with the screw
mount on the main control board.
4. Install the 20-Comm-x board (if used). Torque the four mounting screws
to 2.9 N•m (26 lb•in).
5. Install the HIM cradle/board. Torque the two mounting screws to 3 N•m
(26 lb•in).
6. Install the screw for the green/yellow ground wire from TB11 to the HIM
cradle/board. Torque the screw to 1.6 N•m (14 lb•in).
7. Connect the 8-pin wiring connector to the serial port.
8. Connect the ribbon cable.
9. Replace all safety shields and enclosure covers before applying power to the
drive.