9. Reinstall the DC+ and DC- busbars and torque to 9.0 N•m (80 lb•in).

10. Install stacking panel as detailed on

page 27

.

11. Replace all safety shields and enclosure covers before applying power to the

drive.

Converter Snubber
Resistors - AC Input Only

See

Chapter 1 - Component Diagrams and Torque Specifications

to locate the

component detailed in these instructions.

Remove Components

Kit includes snubber board and resistor.

1. Read and follow the

Safety Precautions on page 12

and

Important Initial

Steps on page 13

.

2. Remove the stacking panel as detailed on

page 26

.

3. Verify the snubber resistor(s) with a volt ohm meter. The reading should

be 8 ohms ± 10%.
• If the reading is not within tolerance, perform the remainder of this

procedure.

• If the reading is within tolerance, do not perform the remainder of this

procedure.

4. For the R snubber resistor only: Remove the transitional busbar assembly

as detailed on

page 28

.

5. Label and disconnect the wires from snubber resistors that will be replaced.
6. Remove the resistor.

Snubber Resistor for “R” SCR

Snubber Resistor for “S” SCR

Snubber
Resistor for
“T” SCR