Publication 0160-5.18 - June 2003

B-18

DeviceNet Information

Class Code 0xB3 —
160 Parameter Table Object

Instance 1 Attributes

Class Attributes: None Supported

Number of Instances: 1

Attribute ID

Access

Rule

Parameter Name

Data

Type

Units

Description

This Bulletin 160 SSC specific object implements all of the parameters in the 160 SSC parameter table as instance attributes of the object. For example,
attribute #1 corresponds to P01 - [Output Frequency]. This enables you to configure a drive via DeviceNet using attribute numbers that are published as
parameter numbers in the Bulletin 160 SSC User Manual.
Important: Attributes 9 and 12 shown below do not match what is published in the Bulletin 160 SSC User Manual.

01

Get

[Output Frequency]

UINT

0.1 Hz

Frequency at TB2 terminals T1, T2, T3.

02

Get

[Output Voltage]

UINT

1 Volt

Voltage at TB2 terminals T1, T2, T3.

03

Get

[Output Current]

UINT

0.01 Amperes

Current at TB2 terminals T1, T2, T3.

04

Get

[Output Power]

UINT

0.01 kW

Power at TB2 terminals T1, T2, T3.

05

Get

[Bus Voltage]

UINT

1 Volt

DC Bus voltage level.

06

Get

[Cmd Frequency]

UINT

0.1 Hz

Commanded frequency.

07

Get

[Present Fault]

USINT

Numeric Value

Coded last fault number.

08

Get

[Heatsink Temp]

USINT

1 C

Temperature of the drive heatsink.

09

Get

[Drive Status]

WORD

Binary Number

Status of drive in binary coded format.

10

Get

[Drive Type]

USINT

Numeric Value

Used by Allen-Bradley field service personnel.

11

Get

[Control Version]

UINT

Numeric Value

version of drive firmware used.

12

Get

[Input Status]

WORD

Binary Number

Open (0) Closed (1) state of drive’s discrete inputs.

13

Get

[Power Factor Ang]

UINT

0.1

Angle (electrical degrees) between V and I.

14

Get

[Memory Probe]

UINT

Numeric Value

Used by Allen-Bradley service personnel.

15

Get

[Preset Status]

WORD

Binary Number

Displays state of TB3 inputs.

16

Get

[Analog Input]

INT

0.1%

The analog input as a percent of full scale.

17

Get

[Fault Buffer 0]

USINT

Numeric Value

Stores the most recent fault.

18

Get

[Fault Buffer 1]

USINT

Numeric Value

Stores the second most recent fault.

19

Get

[Fault Buffer 2]

USINT

Numeric Value

Stores the third most recent fault.

30

Get/Set

[Accel Time 1]

UINT

0.1 Seconds

Time to ramp from 0 Hz to maximum frequency.

31

Get/Set

[Decel Time 1]

UINT

0.1 Seconds

Time to ramp from maximum frequency to 0 Hz.

32

Get/Set

[Minimum Freq]

USINT

1 Hz

Lowest continuous output frequency.

33

Get/Set

[Maximum Freq]

UINT

1 Hz

Highest continuous output frequency.

34

Get/Set

[Stop Mode Select]

USINT

Numeric Value

Determines stop mode used.

!

ATTENTION: Changing this parameter
value may cause unpredictable network
conditions, resulting in equipment damage,
personal injury, or death. Make sure that
you understand how changing this
parameter affects your application.