Drive program parameters, Drive program parameters -8 – Rockwell Automation 160-DN2 160-DN2 DeviceNet Communication Module FRN 3.xx User Manual

Page 36

Advertising
background image

Publication 0160-5.18 - June 2003

5-8

DeviceNet Parameter Descriptions

Drive Program Parameters

Below is a brief description of the Bulletin 160 SSC Interface
Program Group parameters. Refer to the Bulletin 160 SSC User
Manual
for more detailed information on these parameters.

Parameter

Number

Parameter Name

Object Mapping

(Class-Instance-

Attribute)

Description

Units

30

[Accel Time 1]

0xB3-1-30

Time to ramp from 0 Hz to maximum frequency.

0.1 Seconds

31

[Decel Time 1]

0xB3-1-31

Time to ramp from maximum frequency to 0 Hz.

0.1 Seconds

32

[Minimum Frequency]

0xB3-1-32

Lowest continuous output frequency.

1 Hz

33

[Maximum Frequency]

0xB3-1-33

Highest continuous output frequency.

1 Hz

34

[Stop Mode Select]

0xB3-1-34

Determines stop mode used.

Numeric Value

35

[Base Frequency]

0xB3-1-35

Set to motor’s nameplate frequency.

1 Hz

36

[Base Voltage]

0xB3-1-36

Set to motor’s nameplate voltage.

1 Volt

37

[Maximum Voltage]

0xB3-1-37

Highest voltage the drive will output.

1 Volt

38

[Boost Select]

0xB3-1-38

Sets the volts/Hz relationship.

Numeric Value

39

[Skip Frequency]

0xB3-1-39

Frequency at which drive will not run continuously.

1 Hz

40

[Skip Freq Band]

0xB3-1-40

Used with P39 - [Skip Frequency] to create skip band.

1 Hz

41

[Overload Select]

0xB3-1-41

Selects derating factor for motor overload.

Numeric Value

42

[Motor Overload]

0xB3-1-42

Set to motor nameplate full load amperes.

0.01 Amperes

43

[Current Limit]

0xB3-1-43

Max output current allowed before limiting.

% I rating

44

[DC Hold Time]

0xB3-1-44

DC Injection Braking duration.

0.1 Seconds

45

[DC Hold Voltage]

0xB3-1-45

Voltage level for DC Injection Braking.

1 Volt

46

[Input Mode]

0xB3-1-46

Type of START, STOP, REV, commands.

Numeric Value

47

[Output Configure]

0xB3-1-47

Configures TB3 output relay functionality.

Numeric Value

48

[Output Threshold]

0xB3-1-48

Used in conjunction with P47 - [Output Configure].

Numeric Value

49

[PWM Frequency]

0xB3-1-49

Carrier frequency for PWM output waveform.

0.1 kHz

50

[Restart Tries]

0xB3-1-50

Times drive will attempt to reset a fault.

Numeric Value

51

[Restart Time]

0xB3-1-51

Time between restart attempts.

0.1 Seconds

52

[DB Enable]

0xB3-1-52

Enables/disables dynamic braking.

Numeric Value

53

[S-Curve]

0xB3-1-53

Enables a fixed shape S-curve.

Numeric Value

!

ATTENTION: Changing this parameter
value may cause unpredictable network
conditions, resulting in equipment damage,
personal injury, or death. Make sure that
you understand how changing this
parameter affects your application.

!

ATTENTION: Changing this parameter
value may cause unpredictable network
conditions, resulting in equipment damage,
personal injury, or death. Make sure that
you understand how changing this
parameter affects your application.