Class code 0x05 - connection object, Class code 0x05 — connection object – Rockwell Automation 160-DN2 160-DN2 DeviceNet Communication Module FRN 3.xx User Manual
Page 88

Publication 0160-5.18 - June 2003
B-6
DeviceNet Information
Class Code 0x05 —
Connection Object
Instance 1 Attributes: Explicit Message Instance
Class Attributes: None Supported
Number of Instances: 3
Attribute ID
Access Rule
Name
Data Type
Value
1 Get
State
USINT
0 = Nonexistant
1 = Configuring
3 = Established
4 = Timed out
5 = Deferred delete
2
Get
Instance Type
USINT
0 = Explicit Message
3
Get
Transport Class Trigger
USINT
0x83
4 Get
Produced
Connection
ID
UINT
10xxxxxx100
where xxxxxx = Node address
5
Get
Consumed Connection ID
UINT
10xxxxxx100
where xxxxxx = Node address
6
Get
Initial Comm. Characteristics
USINT
0x22
7 Get
Produced
Connection
Size
UINT
7
8
Get
Consumed Connection Size
UINT
7
9
Get/Set
Expected Packet Rate
UINT
Timer resolution of 10 msec.
12 Get/Set
Watchdog
Action
USINT
1 = Auto delete
3 = Deferred delete
13
Get
Produced Connection Path Length
UINT
0
14
Get
Produced Connection Path
Null (no data)
15
Get
Consumed Connection Path Length
UINT
0
16
Get
Consumed Connection Path
Null (no data)