Class code 0x05 — connection object (continued) – Rockwell Automation 160-DN2 160-DN2 DeviceNet Communication Module FRN 3.xx User Manual
Page 89

Publication 0160-5.18 - June 2003
DeviceNet Information
B-7
Class Code 0x05 —
Connection Object (Continued)
Instance 2 Attributes: Polled I/O Message Connection
Attribute ID
Access Rule
Name
Data Type
Value
1 Get
State
USINT
0 = Nonexistant
1 = Configuring
3 = Established
4 = Timed out
2
Get
Instance Type
USINT
1 = I/O Message
3
Get
Transport Class Trigger
USINT
0x82
4 Get
Produced
Connection
ID
UINT
10xxxxxx100
where xxxxxx = Node address
5
Get
Consumed Connection ID
UINT
10xxxxxx101
where xxxxxx = Node address
6
Get
Initial Comm Characteristics
USINT
0x21
7
Get
Produced Connection Size
UINT
0 to 8
8
Get
Consumed Connection Size
UINT
0 to 4
9
Get/Set
Expected Packet Rate
UINT
Timer resolution of 10 msec.
12 Get/Set
Watchdog
Action
USINT
0 = Transition to timed out
1 = Auto delete
2 = Auto reset
13
Get
Produced Connection Path Length
UINT
3
14 Get/Set
Produced
Connection
Path
[63hex][hex string]
where [hex string] is the input assembly
number in hex
15
Get
Consumed Connection Path Length
UINT
3
16
Get/Set
Consumed Connection Path
[63hex][hex string]
where [hex string] is the output
assembly number in hex