Understanding the fault led (continued) – Rockwell Automation 160-DN2 160-DN2 DeviceNet Communication Module FRN 3.xx User Manual

Page 78

Advertising
background image

Publication 0160-5.18 - June 2003

7-4

Troubleshooting

Understanding the FAULT LED
(Continued)

Table 7.B Bulletin 160 SSC Interface Fault Codes (Continued)

Fault Code

Fault

Indication

Description

Corrective Action

43

VW Short

Excessive current has been detected between these
two drive output terminals.

Check the motor and external wiring to the drive output
terminals for a shorted condition.

46

Intermittent Phase

Fault

An external short occurred while running diagnostics.

Check wiring between the drive and the motor. Check for
more than one shorted output.

48

Reprogramming

Fault

Occurs when reset defaults is performed.

Clear fault.

50

No DeviceNet Power 24 volt network power is not detected.

Check DeviceNet connector at module. Also, check the
network’s power supply.

51

DeviceNet Module

EEPROM Fault

DeviceNet 160-DN2 module EEPROM has invalid data. Reset to factory defaults P56 - [Reset Functions].

52

DeviceNet Lost

I/O Connection

Polled I/O connection timed out.

Check DeviceNet Master for correct operation (i.e.,
powered up, scanner online, etc.).

53

DeviceNet

Unrecoverable Fault

No communication is occurring. Fault occurs when
duplicate node address exists or wrong baud rate is set.

Check DIP switch settings for proper baud rate and node
address.

54

DeviceNet Transmit

Fault

A transmit timeout occurred.

Power drive off and then cycle power on.

55

Forced Fault

Control Supervisor Object (Class Code 0x29) attribute
17 was set to 1.

Clear fault.

56

Drive Incompatibility

Fault

The 160-DN2 module is not compatible with the 160
SSC drive firmware version (e.g., Series C FRN 7.02)

Replace the drive.

Table 7.C DeviceNet Fault Codes (Class 0x29, Instance 1, Attribute 13)

Fault Code

(hex)

Fault

Indication

Description

Corrective Action

1100

Max Retries Fault

Drive failed to reset fault within the maximum retries
specified.

Repair system fault.

2213

Power Test

Fault detected during initial start sequence.

Check drive wiring. Check motor wiring. Reset drive to
factory defaults.

2220

Over Current

Overcurrent detected in hardware trip circuit.

Check short circuit at the drive output or excessive load
conditions at the motor.

2331

Phase U

Phase to ground fault detected between drive and motor
phase U.

Check wiring between drive and motor. Check motor for
grounded phase.

2332

Phase V

Phase to ground fault detected between drive and motor
phase V.

Check wiring between drive and motor. Check motor for
grounded phase.

2333

Phase W

Phase to ground fault detected between drive and motor
phase W.

Check wiring between drive and motor. Check motor for
grounded phase.

2341

UV Short

Excessive current has been detected between these
two drive output terminals.

Check the motor and external wiring to the drive output
terminals for a shorted condition.