Enabling network control, Configuring drive input mode, Enabling network control -7 – Rockwell Automation 160-DN2 160-DN2 DeviceNet Communication Module FRN 3.xx User Manual
Page 45: Configuring drive input mode -7

Publication 0160-5.18 - June 2003
Using 160-DN2 with DeviceNet Scanner
6-7
Enabling Network Control
The 160-DN2 module must be configured to accept commands from
the network. To do this, configure the drive “Input Mode” parameter
(
Configuring Drive Input Mode
1. In the Current Value column, click on the value for Parameter 46
- [Input Mode] and select “Network Control” from the dropdown
list.
Important: Remember to jumper or close drive Terminals 7 and
8 on TB2 before the drive can start.
2. Click Apply to save the changes.
Figure 6.5
Network Control Screen
!
ATTENTION: Changing this parameter value may
cause unpredictable network conditions, resulting in
equipment damage, personal injury, or death. Ensure
that you understand how changing this parameter
affects your application.