Electrical installation

To meet the requirements of the relevant product standards (e.g. EN 61 496­1), the
external voltage supply for the devices (SELV) must be able to bridge a brief mains
failure of 20 ms. Power supplies according to EN 60 204­1 satisfy this requirement.
Suitable power supplies are available as accessories from Rockwell Automation (see
“Accessories” section on page 53).

Dimension the electrical protection for the camera to suit the information in the
“Data sheet” section on page 47.

System connection M12

× 8

Figure 20 - System connection SC300

The SC300 has a hard-wired connector cable (length: approx. 30 cm) with a cable plug
M12 × 8.

Table 9 - Pin assignment system connection SC300

Note

Connecting cables of different length are available as accessories from Rockwell
Automation (see “Accessories” section on page 53). If you use connecting cables you have
assembled yourself, ensure the functional earth (pin 8) is connected.

Connecting the SC300

Without external device monitoring (EDM), without internal restart interlock
and without external key-operated pushbutton for teach-in

Note

If you use the SC300 without the internal restart interlock, then you must implement the
restart interlock externally, i.e. machine-side.

Pin

Color

Signal

Function

1

White

RESTART

Reset/restart (optional)

2

Brown

+24V DC

24V DC (voltage supply)

3

Green

TEACH/SYNC

Teach-in/synchronization

4

Yellow

EDM

External device monitoring (EDM) (optional)

5

Grey

OSSD1

OSSD1 (safe output signal switching device 1)

6

Pink

OSSD2

OSSD2 (safe output signal switching device 2)

7

Blue

GND

0V DC (voltage supply)

8

FE

Functional earth