34

Rockwell Automation Publication 10000202762 Ver 00 - January 2012

Chapter 5

Electrical installation

Figure 28 - SC300 safety camera configured for automatic restart with external teach connected
to a GSR DI safety relay module configured for automatic restart and also showing an E-Stop
switch connection.

Principle of operation

When the light path on the SC300 safety camera is clear and the input conditions on the
GSR DI safety relay module are valid, the system is ready for switch on and waits for an
input signal/switch on signal. The system’s corresponding logic path is enabled by
pressing and releasing the related restart switch. The related outputs of the GSR DI carry
power. If the input conditions are no longer met, the related outputs of the GSR DI shut
down.

The restart switch/button must be used to restart the system.

Power

In1
In2
Out
Logic

A2

A1

+

-

S11

S21

S12

S22

S32

S42

L12

L11

Y32

S34

13

14

23

24

24VDC

IN1

DI

IN2

0 1

2

3

4

5

6

7

8

LOGIC

Test Out

Teach

Camera Pigtail

889D-F8AB-X

Wht

Yel

Blu

Red

Gry

Brn

Grn

Pnk

K1

K2

L1 L2 L3

M

Wht 1 Reset

Color Pin Signal

Brn 2 +24V
Grn 3 Teach

Yel 4 EDM

Gry 5 OSSD 1

Pnk 6 OSSD 2

Blu 7 0V DC

Red 8 FE

K1

K2

24V DC

0V DC

E-Stop

Start/
Restart

Stop

K1

K2