Annex, Chapter, Checklist for the manufacturer – Rockwell Automation 442L SC300 Safety Sensor User Manual User Manual

Page 56

Advertising
background image

54

Rockwell Automation Publication 10000202762 Ver 00 - January 2012

Chapter 13

Annex

Chapter

13

Annex

Checklist for the manufacturer

Checklist for the manufacturer/installer for the installation of electro-sensitive protective equipment (ESPE)

Details about the points listed below must be present at least during initial commissioning — they are, however, dependent on the respective application, the specifications of which
are to be controlled by the manufacturer/installer.
This checklist should be retained and kept with the machine documentation to serve as reference during recurring tests.

1.

Have the safety rules and regulations been observed in compliance with the directives/standards applicable to the machine?

Yes

No

2.

Are the applied directives and standards listed in the declaration of conformity?

Yes

No

3.

Does the protective device comply with the required PL/SILCL and PFHd as per EN ISO 13 849­1/EN 62 061 and the type as per EN 61 496­1?

Yes

No

4.

Is the access to the hazardous point only possible through the protective field of the ESPE?

Yes

No

5.

In the case of hazardous point protection, have appropriate measures been taken to prevent (mechanical point-of-operation guarding) or monitor
unprotected presence in the hazardous area and have these been secured against removal?

Yes

No

6.

Are additional mechanical protective measures fitted and secured against manipulation which prevent reaching under, over or around the ESPE?

Yes

No

7.

Has the maximum stopping and/or stopping/run-down time of the machine been measured, specified and documented (at the machine and/or in the
machine documentation)?

Yes

No

8.

Has the ESPE been mounted such that the required safety distance from the nearest hazardous point has been achieved?

Yes

No

9.

Are the ESPE devices correctly mounted and secured against manipulation after adjustment?

Yes

No

10. Are the required protective measures against electric shock in effect (protection class)?

Yes

No

11. Is the control switch for resetting the protective device (ESPE) or restarting the machine present and correctly installed?

Yes

No

12.

Are the outputs on the ESPE (OSSD, AS­Interface Safety at Work interface) integrated in accordance with the required PL/SILCL as per EN ISO 13 849/
EN 62 061, and do they comply with the circuit diagrams?

Yes

No

13. Has the protective function been checked in compliance with the test notes of this documentation?

Yes

No

14. Are the given protective functions effective at every setting of the operating mode selector switch?

Yes

No

15. Are the switching elements activated by the ESPE, e.g. contactors, valves, monitored?

Yes

No

16. Is the ESPE effective over the entire period of the dangerous state?

Yes

No

17.

Once initiated, will a dangerous state be stopped when switching the ESPE on or off and when changing the operating mode, or when switching to
another protective device?

Yes

No

18. Has the information label for the daily check been attached so that it is easily visible for the operator?

Yes

No

This checklist does not replace the initial commissioning, nor the regular inspection by qualified safety personnel.