Chapter 5 Programmable Parameters

Table 40 - Single/Three Phase & FLA Setting Parameters Detail

Table 41 - FLA Setting Ranges & Default Values (with indicated setting precision)

SINGLE/THREE PH

This parameter allows the installer to

configure the E3 for single-phase or three-

phase mode. When set to single-phase

mode, the E3 will report L3 monitoring

parameters as 0 and only use L1 and L2 to

calculate Average, Imbalance, and total

monitoring parameters.

Parameter Number

27

Access Rule

Get/Set

Data Type

BOOL

Object Mapping

2C

hex

-1-127

Group

Overload Setup

Units

—

Minimum Value

0 = Single Phase

Maximum Value

1 = Three Phase

Default Value

1

FLA SETTING

The motor’s full load current rating is

programmed in this parameter. Refer to

Chapter 3 for instructions related to service

factor, maximum continuous rated (MCR)

motors, and wye-delta (star-delta)

applications.

This parameter is used to program the low-

speed FLA value of a two-speed motor.

Parameter Number

28

Access Rule

Get/Set

Data Type

UINT

Object Mapping

2C

hex

-1-225

2C

hex

-1-3

2C

hex

-1-224

Group

Overload Setup

Units

Amps

Minimum Value

See

Table 41

Maximum Value

See

Table 41

FLA Current Range (A)

Default Value CT Ratio Selection

➊

Min

Max

0.040

2.00

0.040

—

1.00

5.00

1.00

—

3.00

15.00

3.00

—

5.00

25.00

5.00

—

9.0

45.0

9.0

—

18.0

90.0

18.0

—

9

45

9

50:5

18

90

18

100:5

28

140

28

150:5

42

210

42

200:5

60

302

60

300:5

84

420

84

500:5

125

630

125

600:5

172

860

172

800:5

240

1215

240

1200:5

450

2250

450

2500:5

1000

5000

1000

5000:5

➊

Devices with an FLA setting range of 9…5000 A.