142

Rockwell Automation Publication 193-UM002I-EN-P - December 2011

Chapter 6 Monitoring Parameters

➊ Series C and later

WARNING STATUS

This parameter provides warning
identification.

Parameter Number

15

Access Rule

Get

Data Type

WORD

Object Mapping

0x29-1-115

Group

Monitor

Units

—

Minimum Value

—

Maximum Value

—

Default Value

None

Bit

Function:

15 14 13 12 11 10 9

8

7

6

5

4

3

2

1

0

—

X

Overload

—

X

Ground Fault (E3 Plus)

—

X

Jam

X

Underload

X

PTC (E3 Plus)

X

Current Imbalance

X

Comm Fault

X

Comm Idle

—

X

Config Fault

X

PM - # Starts

➊

X

PM – Oper. Hours

➊

TRIP LOG 0

This parameter records the latest trip.

Parameter Number

16

Access Rule

Get

Data Type

WORD

Object Mapping

0x29-1-116

Group

Monitor

Units

—

Minimum Value

See Trip Status table

Maximum Value

See Trip Status table

Default Value

None

TRIP LOG 1

This parameter records the trip previous to
Trip Log 0.

Parameter Number

17

Access Rule

Get

Data Type

WORD

Object Mapping

0x29-1-117

Group

Monitor

Units

—

Minimum Value

See Trip Status table

Maximum Value

See Trip Status table

Default Value

None