Appendix B DeviceNet™ Information
Control Supervisor ODVA Fault and Warning Codes
Table 116 - Control Supervisor Object Common Services
Service
Code
Implemented for:
Service
Name
Class
Instance
0x0E
Yes
Yes
Get_Attribute_Single
0x10
No
Yes
Set_Attribute_Single
Table 117 - Control Supervisor ODVA Fault and Warning Codes
Warning/Trip Name
Code
EC1, EC2, EC3
EC5
Test Trip
10
x
x
Remote Trip
11
x
x
Thermal Overload
21
x
x
Phase Loss
22
x
x
L1 Loss
23
L2 Loss
24
L3 Loss
25
Phase Imbalance
26
x
x
Ground Fault
27
x
x
Jam
28
x
x
Underload
29
x
x
Under Voltage L-L
51
x
Over Voltage L-L
52
x
Voltage Unbalance
53
x
Phase Rotation
54
x
Hardware / Config Flt
60
x
x
Non-Volatile Memory
62
x
x
Starts/Hour Exceeded
73
x
x
Stall
101
x
x
Comm Fault
102
x
x
Comm Idle Fault
103
x
x
PTC Fault
104
x
PM Starts
105
x
x
PM Oper Hours
106
x
x
L1 Undercurrent
107
L2 Undercurrent
108
L3 Undercurrent
109
L1Overcurrent
110
L2Overcurrent
111
L3Overcurrent
112