Rockwell Automation 193-EC1_2_3_5, 193-ECPM,592-EC1_2_3_5 E3 and E3 Plus Solid-State Overload Relay User Manual User Manual
Page 33

Rockwell Automation Publication 193-UM002I-EN-P - December 2011
33
Installation & Wiring Chapter 2
Table 14 - IEC per EN60947-4-1
Table 15 - NEMA Contactors
Cat. No. 193-
EC1, EC2,
EC3, EC4, EC5
Contactor
100-
Max.
Starter
FLC [A]
Short-Circuit Current
Max.
Voltage
[V]
Class J Fuse [A]
Prospective
I
r
[A]
Conditional
I
q
[A]
with
Type I
with
Type II
_B
C09
9
1,000
100,000
600
20
15
C12
12
20
20
C16
16
30
30
C23
23
40
40
_D
C30
30
3,000
100,000
600
50
50
C37
37
50
50
C43
43
70
70
_E
C60
60
3,000
100,000
600
80
80
C72
72
100
100
C85
85
5,000
150
150
FF, ZZ
D95
95
10,000
100,000
600
200
200
D110
110
200
200
D140
140
250
250
GF, ZZ
D180
180
10,000
100,000
600
300
300
GG, ZZ
D210
210
10,000
100,000
600
400
400
D250
250
400
400
D300
300
500
500
HG, ZZ
D210
210
10,000
100,000
600
400
400
D250
250
400
400
D300
300
500
500
JG, ZZ
D300
300
10,000
100,000
600
500
500
D420
420
600
600
Cat. No.
592-EC
Contactor
Size
Max.
Starter
FLC [A]
Short-Circuit Current
Max.
Voltage
[V]
Class J Fuse [A]
Prospective
I
r
[A]
Conditional
I
q
[A]
with
Type I
with
Type II
_T
00
9
1,000
100,000
600
20
20
_C
0, 1
18, 27
3,000
30
30
2
45
60
60
_D
3
90
5,000
200
200