Rockwell Automation 193-EC1_2_3_5, 193-ECPM,592-EC1_2_3_5 E3 and E3 Plus Solid-State Overload Relay User Manual User Manual
Page 149

Rockwell Automation Publication 193-UM002I-EN-P - December 2011
149
Voltage Parameters Chapter 7
V Warn Status
This parameter provides voltage based
warning identification as outlined in the
table below:
1 = Warning
0 = No Warning
Parameter Number
161
Access Rule
Get
Data Type
UINT
Object Mapping
0Fhex-A1-01
Group
Voltage monitor
Units
—
Minimum Value
—
Maximum Value
—
Default Value
—
Bit
Function:
15 14 13 12 11 10 9
8
7
6
5
4
3
2
1
0
X
Voltage Hardware Fault
X
Under Volt L-L
X
Over Volt L-L
X
Voltage Unbalance
X
Phase Rotation
X
Under Frequency
X
Over Frequency
L1-L2 Voltage
This parameter provides the L1-L2 voltage
measurement in Volts.
Parameter Number
162
Access Rule
Get
Data Type
UINT
Object Mapping
0Fhex-A2-01
Group
Voltage Monitor
Units
Volt
Minimum Value
0
Maximum Value
65545
Default Value
—
L2-L3 Voltage
This parameter provides the L2-L3 voltage
measurement in Volts.
Parameter Number
163
Access Rule
Get
Data Type
UINT
Object Mapping
0Fhex-A3-01
Group
Voltage Monitor
Units
Volt
Minimum Value
0
Maximum Value
65545
Default Value
—
L3-L1 Voltage
This parameter provides the L3-L1 voltage
measurement in Volts.
Parameter Number
164
Access Rule
Get
Data Type
UINT
Object Mapping
0Fhex-A4-01
Group
Voltage Monitor
Units
Volt
Minimum Value
0
Maximum Value
65545
Default Value
—