Power setup group – Rockwell Automation 193-EC1_2_3_5, 193-ECPM,592-EC1_2_3_5 E3 and E3 Plus Solid-State Overload Relay User Manual User Manual
Page 171

Rockwell Automation Publication 193-UM002I-EN-P - December 2011
171
Power Parameters Chapter 8
Power Setup Group
PW Trip Enable
This parameter allows the installer to
enable or disable power based trip
functions separately.
1 = Trip
0 = No TrIp
Parameter Number
225
Access Rule
Get/Set
Data Type
UINT
Object Mapping
0Fhex-E1-01
Group
Power Setup
Units
—
Minimum Value
—
Maximum Value
—
Default Value
—
Bit
Function:
15 14 13 12 11 10 9
8
7
6
5
4
3
2
1
0
X
Under Real Pwr
X
Over Real Pwr
X
Under Con kVAR
X
Over Con kVAR
X
Under Gen kVAR
X
Over Gen kVAR
X
Under Power kVA
X
Over Power kVA
X
Under PF Lagging
X
Over PF Lagging
X
Under PF Leading
X
Over PF Leading
X
Power Overflow
PW Warn Enable
This parameter allows the installer to
enable or disable power based warning
functions separately.
1 = Warning
0 = No Warning
Parameter Number
226
Access Rule
Get/Set
Data Type
UINT
Object Mapping
0Fhex-E2-01
Group
Power Setup
Units
—
Minimum Value
—
Maximum Value
—
Default Value
—
Bit
Function:
15 14 13 12 11 10 9
8
7
6
5
4
3
2
1
0
X
Under Real Pwr
X
Over Real Pwr
X
Under Con kVAR
X
Over Con kVAR
X
Under Gen kVAR
X
Over Gen kVAR
X
Under Power kVA
X
Over Power kVA
X
Under PF Lagging
X
Over PF Lagging
X
Under PF Leading
X
Over PF Leading
X
Power Overflow