Chapter 2 Installation & Wiring
Table 6 - Maximum Wire Length (PTC & input)
Table 7 - Ground Fault Sensor Terminals (S1 & S2)
Flexible-Stranded with Ferrule Metric Single
0.25…2.5 mm
2
Multiple
0.5...0.75 mm
2
0.55 Nm
Coarse-Stranded/Solid Metric
Single
0.2...2.5 mm
2
Multiple
0.2...1.5 mm
2
0.55 Nm
Minimum Cross Section
mm
2
0.5
0.75
1.5
2.5
4.0
AWG
20
18
16
14
12
Maximum Length ➊
meters
160
250
400
600
1000
feet
525
825
1300
1950
3200
➊
The use of shielded cable is recommended for the PTC thermistor circuit to assist in
obtaining compliance with Electromagnetic Compatibility (EMC) requirements.
Shielded cable is recommended for the input circuits, where wire lengths exceed 200
meters (656 feet).
NOTE:
For reliable input signal processing, input wiring should be routed in raceways
separate from power cabling.
Wire Type
Shielded, Twisted Pair
Cross Section
0.2…4.0 mm
2
(#24…12 AWG)
Torque
0.55 N
·
m (5 lb.-in.)
Wire Type
Conductor Torque All Cat. No. Types