Chapter 5 Programmable Parameters
Table 55 - Current Imbalance Parameters Detail
CI INHIBIT TIME
This parameter defines the amount of time
current imbalance detection is inhibited
during a motor starting sequence.
Parameter Number
49
Access Rule
Get/Set
Data Type
USINT
Object Mapping
2C
hex
-1-149
Group
Advanced Setup
Units
Seconds
Minimum Value
0
Maximum Value
250
Default Value
10
CI TRIP DELAY
This parameter allows the installer to
program a time duration that a current
imbalance condition must exist at the
programmed level prior to the device
tripping.
Parameter Number
50
Access Rule
Get/Set
Data Type
USINT
Object Mapping
2C
hex
-1-150
Group
Advanced Setup
Units
Seconds
Minimum Value
0.1
Maximum Value
25.0
Default Value
5.0
CI TRIP LEVEL
This parameter sets the current imbalance
trip level.
Parameter Number
51
Access Rule
Get/Set
Data Type
USINT
Object Mapping
2C
hex
-1-151
Group
Advanced Setup
Units
%
Minimum Value
10
Maximum Value
100
Default Value
35
CI WARN LEVEL
This parameter sets the current imbalance
warning level.
Parameter Number
52
Access Rule
Get/Set
Data Type
USINT
Object Mapping
2C
hex
-1-152
Group
Advanced Setup
Units
%
Minimum Value
10
Maximum Value
100
Default Value
20