Rockwell Automation 193-EC1_2_3_5, 193-ECPM,592-EC1_2_3_5 E3 and E3 Plus Solid-State Overload Relay User Manual User Manual

Page 90

Advertising
background image

90

Rockwell Automation Publication 193-UM002I-EN-P - December 2011

Chapter 3 Protective Trip & Warning Functions

Table 23 - Protective Warning Summary

Function

Factory

Default

Warning Level

Inhibit Time

➊

Range

Default Range

Default

Overload

Disabled

0…100%

➋

85%

Phase Loss

Ground Fault (193/592-EC2)

Disabled

Internal 1…5 A

2.0 A

0…250 s

10 s

Ground Fault (193/592-EC3)

External 0.02…5 A

➌

Stall

Jam

Disabled

50…600%

150%

0…250 s

10 s

Underload

10…100%

➍

70%

Thermistor (PTC)

Current Imbalance

10…100%

20%

0…250 s

10 s

Comm Fault

Comm Idle

Voltage Input Module

Hardware Fault

➎

Enabled

Under Voltage L-L

➎

Disabled

0...65535

400

0…250 s

10 s

Over Voltage L-L

➎

Voltage Unbalance

➎

0…100

85

Phase Rotation

➎

1…2

1

Under Frequency

➎

0…250

58

Over Frequency

➎

62

Under Real Power

➎

0…32767

Over Real Power

➎

Under Consumed kVAR

➎

Over Consumed kVAR

➎

Under Generated kVAR

➎

-32767…0

Over Generated kVAR

➎

Under Power kVA

➎

0…32767

Over Power kVA

➎

Under Power Factor Lagging

➎

-100…0

-95

Over Power Factor Lagging

➎

-90

Under Power Factor Leading

➎

0...100

95

Over Power Factor Leading

➎

90

➊

The inhibit time setting parameters are applicable to both the trip and warning functions.

➋

Overload warning setting is entered as a percentage of the thermal capacity utilized.

➌

Must use Ground Fault Sensors (Catalog Number 193-CBCT_).

➍

50…100% for devices with FRN 1.003 and earlier.

➎

Available on 193/592-EC5 only.