Protective Trip & Warning Functions Chapter 3

Table 22 - Protective Trip Summary

Function

Factory Default

Trip Level

Trip Delay

Inhibit Time

➊

Range

Default

Range

Default

Range

Default

Overload

Enabled

➋

Trip Class

5…30

Trip Class

10

Phase Loss

➌

0.1…25.0 s

1.0 s

0…250 s 0 s

Ground Fault (193/592-EC2)

Disabled

Internal 1…5 A

2.5 A

0.0…25.0 s

0.5 s

0…250 s 10 s

Ground Fault (193/592-EC3)

External 0.02…5 A

➍

2.5 A

0.0…25.0 s

0.5 s

0…250 s 10 s

Stall

100…600%

➎

600%

➎

0…250 s

➎

10 s

➎

Jam

50…600%

250%

0.1…25.0 s

5.0 s

0…250 s 10 s

Underload

10…100% FLA

➏

50%

0.1…25.0 s

5.0 s

0…250 s 10 s

PTC

Current Imbalance

10…100%

35%

0.1…25.0 s

5.0 s

0…250 s 10 s

Comm Fault

Enabled

Comm Idle

Disabled

Remote Trip

Voltage Input Module

Hardware Fault

➐

Undervoltage L-L

➐

0...65535

100

0.1…25.0 s

1.0 s

0…250 s

10 s

Overvoltage L-L

➐

0...65535

500

Voltage Unbalance

➐

0…100

75

Phase Rotation

➐

1…2

1

Under Frequency

➐

0…250

57

0.1…25.0 s

1.0 s

Over Frequency

➐

0…250

63

Under Real Power

➐

0…32767

Over Real Power

➐

Under Consumed kVAR

➐

Over Consumed kVAR

➐

Under Generated kVAR

➐

-32767…0

Over Generated kVAR

➐

-32767…0

Under Power kVA

➐

0…32767

Over Power kVA

➐

0…32767

Under Power Factor Lagging

➐

-100…0

-90

Over Power Factor Lagging

➐

-100…0

-95

Under Power Factor Leading

➐

0...100

90

Over Power Factor Leading

➐

0...100

95

➊

The inhibit time setting parameters are applicable to both the trip and warning functions.

➋

FLA Setting range and default values are dependent upon the current rating of the product. See the user manual for more information.

➌

Phase loss trip level is factory-set at a current imbalance greater than or equal to 100% and is not user-adjustable.

➍

Must use Ground Fault Sensors (Catalog Number 193-CBCT_).

➎

Stall protection is only applicable during the motor starting sequence. If any phase of current falls below the programmed Stall Trip Level, stall

protection is disabled.

➏

50…100% for devices with FRN 1.003 and earlier.

➐

Available on 193/592-EC5 only.